5.6.1.4. Trigger modes
Acronym App / GF_eXpress menu Attribute Retentive U.M. Default
Description
hd.5
Power Control R/W
■
- 1
Trigger mode selection.
Options:
5.6.1.5. Minimum number of Burst Firing cycles
Acronym App / GF_eXpress menu Attribute Retentive U.M. Default
Description
bF.Cy
Power Control R/W
■
- 1
Minimum number of burst fire cycles (full waves) in BF mode.
min...max: 1 ...10
5.6.1.6. SSR output cycle time
Acronym App / GF_eXpress menu Attribute Retentive U.M. Default
Description
Ct
Power Control R/W
■
s 2.0
SSR output cycle time in fixed cycle time (FCT) mode.
Example: if set to 10.0 if the requested power to be supplied is 75.0%, the On phase (SSR operating)
will last 7.5 s, the Off phases (SSR not operating) will last 2.5 s.
min...max: 0.1 ... 30.0 s
0 FCT - Fixed Cycle Time
1 BF - Burst Firing
2 HSC - Half Single Cycle
3 PA - Phase Angle