5.6.1.4. Enabling softstart at shutdown
Acronym App / GF_eXpress menu Attribute Retentive U.M. Default
Description
PS.S.E
Power Control R/W
- 0
Enabling softstart ramp at shutdown in ON/OFF software switching.
Options:
Status
5.6.1.5. Soft start ramp status
Acronym App / GF_eXpress menu Attribute Retentive U.M. Default
Description
STATUS3
Expert Status Diagnostic
R - - -
Soft start ramp status.
0 Shutdown ramp disabled
1 Shutdown ramp enabled
bit Meaning
2 Phase soft start on
3 Phase soft start end
5.6.2. Current limit settings
For GRM-H-x-x-x-AC-x-x-x-x-x and GRM-Hx-
x-x-FB-x-x-x-x-x models only
It is possible to limit the peak current during the
softstart ramp or the RMS current during
steady state operations (when any softstart ramp is
finished).
5.6.2.1. Peak current limiter during softstart
Acronym App / GF_eXpress menu Attribute Retentive U.M. Default
Description
Cu.S.E
Power Control R/W
- 0
Peak current limitation enabled during the softstart phase.
Options:
0 Disabled
1 Enabled