819XX_MAN_GRM-H_11-2022_ENG_pag. 90
INPUTS
Analogue command input (Versions with AN input type)
Function Proportional power control signal
Maximum Error 1% f.s. ± 1 scale point at an ambient temperature of 25°C/ 77°F
Thermal shift <100 ppm/° C on f.s.
Sampling time 10 ms
0-10V scale Input impedance > 500 KΩ
0-5V scales Input impedance > 500 KΩ
0-20mA or 4-20mA scale Internal Shunt Resistance: 250 Ω
Potentiometer input
Potentiometer resistance: 1 KΩ at 47 KΩ
Potentiometer power supply: + 5V (provided by GRM, max 10mA)
Linear input reading scale 0 ... 100.0 %
Common mode immunity -60V, +60V
IO-LINK input (Versions with input type I)
Function IO-LINK fieldbus communication line
Protocol
IO-LINK
Type of transmission: COM2 (38.4 kBaud)
IO-Link version: 1.1.2
SIO mode: Yes
Auxiliary output: Pin 17/ 18-19 Alarm output
Auxiliary input: Pin 14
Line voltage and load current measurement
Load current measurement function Measurement range (full-scale f.s.): 0 ... 1.5 * Irated_product
RMS current measurement accuracy
2% f.s. at room temperature of 25°C / 77°F
Thermal shift: <200 ppm/° C
Line voltage measurement function Working voltage range (full-scale f.s.): 60...660Vac
RMS voltage measurement accuracy
2% f.s. at room temperature of 25°C / 77°F
Thermal shift: <100 ppm/° C
Current and voltage sampling time 10 ms
Line frequency 50/60 Hz
Configurable I/O
I/O pin 13 configurable (only with Analog version)
Function Configurable as digital output or input
Output Function
Configurable alarm output functions (partial / total load break, line fault, thermal
alarm)
Potentiometer power supply 5V (max 10mA)
Output type
Output Type Digital output normally off (configurable as normally active).
PNP type, output voltage: 5Vdc, Iout max = 10mA (not protected against short
circuit)
Function Input (default)
Teach In HB partial breakage alarm threshold calibration (default), SCR logic
control, Proportional control via PWM, On / Off Software, Reset alarms
Input voltage range 5-30V (max 3 mA)
Voltage reading status "0" < 2 V
Voltage reading status "1" > 5 V
Input impedance 17 KΩ
PWM input Max frequency: (1, ..., 100 Hz) Max resolution 1% (0.1ms)
Configurable pin 14 input (only with IO-Link version)
Function Configurable digital input
Function Input
Teach In HB partial breakage alarm threshold calibration, Feedback Calibration,
On / Off Software, Reset alarms, Dry out start / restart, disabled (default).
Input voltage range 5-30V (max 3 mA)
Voltage reading status "0" < 2 V
Voltage reading status "1" > 5 V
Input impedance 17 KΩ
I/O pin 17 (D17 / DQ)
Function Configurable as digital output or input
Function Output (default)
SSR output retransmission (default, for two-phase / three-phase slave control)
Configurable alarm (partial / total load break, line fault, thermal alarm)
Output type
Output Type Digital output normally off (configurable as normally active).
PNP type, output voltage: Us(24Vdc)-0.7Vdc, Iout max = 30mA (not protected
against short circuit)
Function Input
Teach In HB partial breakage alarm threshold calibration, SCR logic command,
Software On / Off, Alarm reset
Input voltage range 5-30V (max 3 mA)
Voltage reading status "0" < 2 V
Voltage reading status "1" > 5 V
Input impedance 17 KΩ
OUTPUTS
Alarm output (pin 18 19)
Function - Configurable alarm output (default): Partial load break, line fault, thermal alarm
Type
Voltage free contact (solid state N.O.) max
characteristics: 30V-150mA
conduction resistance: ≤ 1Ω
COMMUNICATIONS PORTS
Porta microUSB di servizio
Functions with TTL serial cable
Only for initial product configuration, via PC.
Use a PC connected to the GRM, ONLY via the
Gefran adapter cable. The adapter powers the GRM.
Cod. F060800 (PC with USB).
Type Micro USB type B connector
Insulation TTL serial NOT isolated
Funzione Dongle NFC:
Disponibile per la configurazione, lettura di Informazioni sul prodotto e dati di
diagnostica. Utilizzare App scaricabile da PlayStore ed AppleStore e Dongle
NFC (vedi tabella accessori)
POWER (STATIC GROUP)
CATEGORY OF USE
(Tab. 2 EN60947-4-3)
AC 51: resistive or low-inductance loads
AC 55b: infrared lamps
AC56a transformers, resistive loads with high temperature coefficient
Trigger modes
OnOff - Zero crossing firing.
FCT- Fixed Cycle Time - Zero Crossing with constant cycle time (settable in
the range 1...200 sec).
BF - Burst Firing with optimised minimum variable cycle time (Zero crossing
firing).
HSC - Half Single Cycle, corresponds to a Burst Firing which handles half on/off
cycles (Zero crossing firing).
PA - load management by adjusting the power-on phase angle.
It is useful for reducing flicker with short-wave infrared loads.
Softstart ramp in Phase Angle configurable with any configured Firing mode
Delay triggering: First cycle start-up delay (only for ZC, BF, single phase
control mode) Can be set from 0 ° to 90 °.
It is useful for inductive loads (primary transformer) to avoid the current peak
that could in some cases trigger the ultra-rapid fuses for the protection of SCRs.
Feedback and Limit functions (optional)
Peak current or RMS limiting algorithms available. Feedback in current (I,I
2
),
voltage (V, V
2
) or power.
Max. rated voltage 480 V AC 600 V AC
Working voltage range 60-530Vac 60-660Vac
Non-repetitive voltage
(Surge protection level)
1200 Vp 1400 Vp
Rated frequency 50/60Hz with auto-determination
Rated current
GRM Model
15 25 25I 30 30I 40 50 60 75 90 120
15A 25A 25A 30A 30A 40A 50A 60A 75A 90A 120A
Non-repetitive over-current,
(t=20 msec)
620A 620A 1600A 620A 1600A 620A 1600A 1600A 1600A 1500A 1500A
I2t for melting (t = 1… 10msec) A
2
s 1800 1800 12800 1800 12800 1800 12800 12800 12800 11250 11250
critical dv/dt with output disabled 1000 V/μs
Rated impulse withstand voltage 4kV
Rated current in short circuit condition 5kA
Minimum Load Current: 150 mA
Voltage drop over rated current: = < 1,2Vrms
Presenza di corrente di dispersione:
< 3mA
(Maximun value with nominal Voltage and Junction temperature of 125°C /
SCR short circuit (current presence with OFF command).
- HB alarm load interrupted or partially interrupted, up to 8 loads in parallel.
- Automatic calibration of the HB alarm threshold based on the current load level
recommended value for diagnosing a maximum of 5 equal loads in parallel).
So, if the device is left at factory settings, it can manage 2, 3, 4 or 5 loads in
parallel without reconfiguration.
load.
most critical conditions (8 equal loads in parallel), it is necessary that the total
current of the load (not faulty) is at least 30% of the rated current of the GRM
Example: a nominal size 15A GRM commands 8 equal resistors in parallel. To
have an alarm of failure of only one of the 8 loads in parallel, the single load
must have absorption of at least 0.56A, the total load must absorb at least 4.5A
(0.56A * 8 loads).
-20°C - +85°C (-4 ... 185°F)