Super Match
3.2 Outdoor unit control
3.2.1 Outdoor frequency control
A. Compressor running frequency range: 3U19:20-100RPS 3U24:20-94RPS, the others are 20~95RPS
3.2.2 Electronic expansion valve (EEV) control
A: Electronic characteristic
Max. open angle 500 pulse
Driving speed PPS
B: Standard open angle control
In Cool/Dry mode, standard open angle: outdoor ambient temp.≥20
o
C, 250 pulse(E);Outdoor ambient
temp.<20
o
C, 210 pulse(E);
In Heat mode, standard open angle: outdoor ambient temp.≥10
o
C, pulse (E);outdoor ambient
temp.<10
o
C, 210 pulse (E).
E. In order to cooperate the compressor discharging temp. over high protection, the system will enlarge the
EEV open angle. Within 5 minutes after compressor starts up, it will not modify. The detecting period is 30
seconds.
Cooling mode Indoor modication angle
100
o
C<discharging temp.
+50degree/30seconds, it will stop until up to the max. permitted
opening angle
90
o
C< discharging temp.<=100
o
C Keep the angle
<=90
o
C -5degree/30seconds, and reduce to 0 degree gradually
Heating mode Indoor modication angle
100
o
C<discharging temp.
+50degree/30seconds, it will stop until up to the max. permitted
opening angle
90
o
C< discharging temp.<=100
o
C Keep the angle
<=90
o
C -5degree/30seconds, and reduce to 0 degree gradually
3.2.3 4-way valve control in heating
Multi: Protection when 4-way valve can not reverse in heating: 10 minutes later after compressor startup, if
indoor coil average temp. is below 15degree and keeps for 1 minute, the unit will stop and occur the 4-way
valve protection.
compressor ON
OFF
4-way valve ON
OFF
15 S(E)
2 minutes and 55s
3.2.4 Electric heater control
If compressor has not run for a long time, the refrigerant will deposit on the bottom of compressor and mix with
the refrigeranr oil. When re-startup, because low pressure reduces, refrigerant will be segregated from the
refrigerant oil and cause soam in the oil, which will make compressor exhaust a lot of oil. Therefore please stop
heating the compressor bottom to ensure the low pressure in startup period should not go down greatly.
• Ambient temp. TA≤27degree, when compressor stops, the electric heater will be electried.
• When TA≥32degree, or compressor running, the electric heater will be off.
Heater ON
OFF
Ambient temp. TA(℃) 27 32
121

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Haier Super Match 3U24GS2ERA and is the answer not in the manual?

Haier Super Match 3U24GS2ERA Specifications

General IconGeneral
BrandHaier
ModelSuper Match 3U24GS2ERA
CategoryAir Conditioner
LanguageEnglish

Related product manuals