7.1.12 High load protection control
The outdoor system will be stopped if the coil temperature is above 65 for 2 minutes. The indoor
fan will be controlled by the thermostat. The outdoor system can be restarted when the coil
temperature is below 42
and the system has been stopped for 3 minutes. The malfunction will be
stored in the malfunction resume and will not be revealed.
7.1.13 abnormal operation of indoor system
When the outdoor system operates, if the indoor system operation differs from the outdoor system,
the abnormal operation malfunction will be reported. 10s after the report, the indoor system will be
closed.
Outdoor system mode Indoor system mode conflicts
cooling heating yes
cooling cooling no
cooling airflow no
heating heating no
heating airflow yes
heating cooling yes
7.1.14 Malfunction list resume.
Nothing is presented if there is no code list.
The malfunction display will automatically finish in 10 seconds.
The remote control only receives the signals for stop. According to the signals, the malfunction
resume presentation finishes.
The resume restores after the power supply restores.
7.1.15 abnormality confirmation approaches.
1. indoor temperature sensor abnormali t y:
under the operation, the normal temperature ranges from 120 degree to -30 degree. When the
temperature goes beyond this range, the abnormality can be confirmed. If the temperature goes back
into the range, the system will automatically resume.
2 .indoor heat interaction sensor abnormality:
under the operation, the normal temperature ranges from 120 degree to -30 degree. When the
temperature goes beyond this range, the abnormality can be confirmed. If the temperature goes back
into the range, the system will automatically resume.
3 .indoor malfunction:
Out door malfunction: When the indoor system receives the outdoor malfunction codes, it will store
the code into E2 for the malfunction list resume. The indoor system will continue to operate according
to the original status, the malfunction code will not be revealed or processed.
Functions and Control
Domestic air conditioner
240

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Haier Super Match 3U24GS2ERA and is the answer not in the manual?

Haier Super Match 3U24GS2ERA Specifications

General IconGeneral
BrandHaier
ModelSuper Match 3U24GS2ERA
CategoryAir Conditioner
LanguageEnglish

Related product manuals