12 Clintonville Road
Northford, CT 06472-1610 USA
800-289-3473 • FAX 203-484-7118
www.notifier.com
NFS2-3030
Listing Document
PN LS10006-051NF-E:F2 5/19/2022 ECN: 16475
For additional documentation on this product, go to http://esd.notifier.com. This additional documentation for the NFS2-3030 may be used as a refer-
ence only.
1 Installation
Wiring methods used shall be in accordance with Standard for Installation and Classification of Burglar and Holdup Alarm Systems, UL 681.
Wiring methods used shall be in accordance with Standard for Central Station Alarm Services, UL 827.
This product is intended to be installed in accordance with the following:
Follow these guidelines when mounting the product’s backbox:
• Backbox should be installed in a dry, indoor location.
• Recommended temperature for installation of fire panel hardware is between 15.6-16.7°C/60-80°F.
• System operation requirements are 15-27°C/60-80°F and at a relative humidity of 93% ± 2% RH (non-condensing) at 32°C ± 2°C (90°F ± 3°F).
• Locate the backbox so the top edge is 66 inches (1.6764 m) above the surface of the finished floor.
• Access to the cabinet shall be in accordance with NFPA 90, article 110.33.
• Allow sufficient clearance around cabinet for door to swing freely.
NOTE: The term NFS2-3030 is used to refer to the NFS2-3030, NFS2-3030E, and NFS2-3030C.The term FAAST is used to refer to the FAAST
XS, FAAST XM, FAAST XT, and the FAAST XT PRO unless otherwise noted.
NOTE: For Mass Notification applications, Class A circuits called out in this manual are Class X.
• NFPA 70 - National Electrical Code/Article 300 Wiring Methods • UL 2572 - Standard for Mass Notification Systems
• NFPA 72 - Central Station Fire Alarm Systems (Automatic, Manual,
and Waterflow) Protected Premises Unit (requires UDACT/UDACT-2)
• UL 38 Manually Actuated Signaling Boxes
• NFPA 72 - Local (Automatic, Manual, Waterflow and Sprinkler
Supervisory) Fire Alarm Systems
• UL 217 Smoke Detector, Single and Multiple Station
• NFPA 72 - Auxiliary (Automatic, Manual, and Waterflow) Fire Alarm
Systems (requires TM-4)
• UL 228 Door Closers - Holders for Fire Protective Signaling
Systems
• NFPA 72 - Remote Station (Automatic, Manual, and Waterflow) Fire
Alarm Systems
• UL 268 Smoke Detectors for Fire Protective Signaling Systems
• NFPA 72 - Proprietary (Automatic, Manual and Waterflow) Fire Alarm
Systems (Protected Premises Unit)
• UL 268A Smoke Detectors for Duct Applications
• NFPA 72 - Initiating Devices for Fire Alarm Systems • UL 346 Waterflow Indicators for Fire Protective Signaling
Systems
• NFPA 72 - Inspection, Testing and Maintenance for Fire Alarm
Systems
• UL 464 Audible Signaling Appliances
• NFPA 72 - Notification Appliances fir Fire Alarm Systems • UL 521 Heat Detectors for Fire Protective Signaling Systems
• NFPA 12- Standard on Carbon Dioxide Extinguishing Systems • UL 864 Standard for Control Units for Fire Protective Signaling
Systems, 10th Edition
• NFPA 12A - Standard on Halon 1301 Fire Extinguishing Systems • UL 1481 Power Supplies for Fire Protective Signaling Systems
• NFPA 13 - Standard for Installation of Sprinkler Systems • UL 1971 Visual Signaling Appliances
• NFPA 15 - Standard for Water Spray Fixed Systems • UL 2610 Standard for Commercial Premises Security Alarm
Units and Systems
• NFPA 16 - Standard for Deluge-Foam Water Systems • UL 2017 Standard for General-Purpose Signaling Devices and
Systems
• NFPA 17 - Standard for Dry Chemical Extinguishing Systems • ULC-S527-11 Standard for Control Units for Fire Alarm Systems
• NFPA 17A - Standard for Wet Chemical Extinguishing Systems • ULC S524 - Standard for the Installation of Fire Alarm Systems
• NFPA 92 - Standard for Design, Installation and Testing of Smoke-
Control Systems
• EIA-485 and EIA-232 Serial Interface Standards
• NFPA 2001 - Standard for Clean Agent Fire Extinguishing Systems