6 Parameter Description
-
196
-
Group F4: Floor parameters
Function
Code
Name
Setting
Range
Default Unit Property
F4-00 Leveling adjustment 0 to 60 30 mm
★
F4-00 is used to adjust the leveling accuracy at elevator stop.
leveling plate or refer to the description of leveling adjustment in group Fr. The NICE-
3000
new
has the advanced distance control algorithm and adopts many methods to
ensure reliability of direct travel ride. Generally you need not modify this parameter.
Function
Code
Name Setting Range Default Unit Property
F4-01 F6-01 to F6-00 1 -
★
The system automatically changes the value of this parameter during running, and
corrects it at leveling
position (door open limit) after the up slow-down and down slow-down switches
Function
Code
Name Setting Range Default Unit Property
F4-02
position
0 to 65535 1 Pulses
F4-03
position
0 to 65535 34464 Pulses
F4-02 and F4-03 indicate the absolute pulses of the current position of the elevator car
relative to the bottom leveling position.
The position data of the NICE3000
new
in the shaft is recorded in pulses. Each position is
expressed by a 32-bit binary number, where the high 16 bits indicate the high byte of
Function
Code
Name Setting Range Default Unit Property
F4-04 Length 1 of leveling plate 0 to 65535 0 Pulses
★
F4-05 Length 2 of leveling plate 0 to 65535 0 Pulses
★
F4-04 indicates the pulses corresponding to the leveling plate length.
F4-05 indicates the pulses corresponding to the sum of the distances between the up
and down leveling switches and two ends of the leveling plate.