Appendix A Foreign Standards
-
344
-
A.4 Requirements on Cables and Cabling
A.4.1 Requirements for Shielded Cable
1) Use the shielded cable to connect the motor to meet the EMC requirements. The
4-conductor shielded cable is recommended with one conductor as the PE. If the
3-conductor shielded cable is used and the shield cannot meet the conduction
requirements, an additional PE wire must be added.
Recommended cables:
PE
Shield
PE conductor
and shield
PE
Shield
󶙽Cross section of recommended shielded cables
Non-recommended power cables:
Shield
PE
󶙽Cross section of non-recommended shielded cables
2) To suppress emission and conduction of the radio frequency interference
󶍽
󶎀
and conductivity. as shown in Figure A-4.
Cable core
Internal insulator
Copper braid
Copper shield
Insulation jacket
󶙽Braided density of shield
3) The grounding area of the shielded cable must be as large as possible. Fasten the
shield to the metal plate with the metal cable clamp, as shown in the following
󶍾
Metal plateMetal cable clampShielded cable
󶙽Fastening the shield with the metal cable clamp

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Inovance Monarch NICE 3000 new Series and is the answer not in the manual?

Inovance Monarch NICE 3000 new Series Specifications

General IconGeneral
BrandInovance
ModelMonarch NICE 3000 new Series
CategoryController
LanguageEnglish

Related product manuals