3 Peripheral Devices and Options
-
85
-
Peripheral Device Mounting Position Function description
DC reactor
37 kW (F model 45
kW) and above
DC reactor
It is standard
37 kW (F model 45
kW) and above.
Improve the power factor of the input side.
Eliminate the impact of input side higher harmonics on the controller
and reduce conduction and radiation interference generated by the
controller.
Precautions for peripheral device connection of the NICE3000
new
:
■
Do not install the capacitor or surge suppressor on the output side of the controller.
Otherwise, it may cause faults to the controller or damage to the capacitor and
surge suppressor.
■
Inputs/Outputs (main circuit) of the controller contain harmonics, which may
interfere with the communication device connected to the controller. Therefore,
■
Select peripheral devices and options according to actual site conditions and
3.2 Peripheral Device Selection Guide
3.2.1 Selection Guide of Cable, Circuit Breaker, and Contactor
1 Selection guide of I/O cable, circuit breaker, and electromagnetic contactor
Peripheral device selection of the NICE3000
new
Controller
Model
Recommended
Fuse on the
Input Side
Bussmann FWH
Series
Recommended
Circuit Breaker
(A)
Recommended
Contactor
(A)
Recommended
Main Circuit
Cable
(mm
2
)
Recommended
Control Cable
(mm
2
)
Recommended
Grounding Cable
(mm
2
)
NICE-
L-C-2002
FWH-35B 16 12 1 0.75 1
NICE-
L-C-2003
FWH-35B 20 18 2.5 0.75 2.5
220-NICE-
L-C-4007
FWH-35B 25 18 4 0.75 4
220-NICE-
L-C-4011
FWH-40B 40 25 6 0.75 6
220-NICE-
L-C-4015
FWH-50B 50 32 6 0.75 6
220-NICE-
L-C-4018
FWH-60B 50 38 6 0.75 6
220-NICE-
L-C-4018F