9 Description of Functions and Schemes
-
299
-
3 Parameters
Function
Code
Name Setting Range Default
F5-00
Attendant/
Automatic
switchover time
3 to 200 3
F6-41
Program control
selection 2
Bit10: Elevator lock in attendant state 0
F6-43
Attendant function
selection
Bit0: Calls canceled after entering attendant state
Bit1: Not responding to hall calls
Bit2: Attendant/Automatic state switchover
Bit3: Door close at jogging
Bit4: Automatic door close
Bit5: Buzzer tweeting at intervals in attendant state
Bit6: Buzzer tweeting at intervals in attendant state
Bit7: Car call button blinking to prompt
128
Attendant/Automatic switchover
switches over to the automatic (normal) state after the time set in F5-00. After this
running
is completed, the system automatically restores to the attendant state (F6-43 Bit2
must be
set to 1). When F5-00 is smaller than 5, the attendant/automatic switchover function is
disabled.
9.2 Fire Emergency Running
1 Function description (Default setting of the system. Certain actions can be
modied by setting the parameters)
■
The elevator clears car calls and hall calls automatically.
■
■
■
If the elevator is under parallel/group control, it exits the parallel/group control
■
The elevator does not respond to hall calls, and responds to only car calls. Only one
call can be registered.
■
The elevator does not open/close the door automatically. You need to press (jog)
the door open/close button to open/close the door.
■
The light curtain signal input is inactive, and safety edge signal input is active.