6 Parameter Description
-
197
-
These two parameters are automatically recorded during shaft auto-tuning.
For the relationship between the two parameters, see 2.4.1 Leveling Signals.
Function
Code
Name Setting Range Default Unit Property
F4-06 0 to 65535 0 Pulses
★
F4-07 0 to 65535 0 Pulses
★
F4-82 0 to 65535 0 Pulses
★
F4-83 0 to 65535 0 Pulses
★
Group F5: Terminal function parameters
Function
Code
Name Setting Range Default Unit Property
F5-00
Attendant/Automatic
switchover time
3 to 200 3 s
★
switches over to the automatic (normal) state after the time set in this parameter.
After this running is completed, the system automatically restores to the attendant
state (F6-43 Bit2 must be set to 1).
When the value of this parameter is smaller than 5, this function is disabled, and the
system is in the normal attendant state.
Function
Code
Name Setting Range Default Unit Property
F5-01 X1 function selection
0 to 127
33 -
★
F5-02 X2 function selection 35 -
★
F5-03 X3 function selection 34 -
★
··· ···
F5-23 X23 function selection 00 -
★
F5-24 X24 function selection 00 -
★
F5-01 to F5-24 are used to set the signals input to DI terminals X1 to X24. Select
The NICE3000
new
provides 24 low-voltage DIs (X1 to X24), 3 high-voltage DIs (X25 to
X27), and 1 AI (Ai/M). All low-voltage inputs share the COM terminal; when the 24 VDC
voltage is applied, the corresponding input indicator becomes ON.