6 Parameter Description
-
229
-
Function
Code
Name Setting Range Default Unit Property
F8-09
Emergency evacuation
operation speed at power
failure
0.020 to F3-11 0.050 m/s
★
F8-10
Emergency evacuation
operation mode at power
failure
0 to 2 1 -
★
F8-09 is used to set the speed for emergency evacuation operation at power failure.
F8-10 is used to set the emergency evacuation operation mode at power failure.
The values are as follows:
■
0: Motor not running
■
1: UPS
■
2: 48 V battery power supply
See 9.13 Automatic Emergency Evacuation Scheme at Power Failure.
Function
Code
Name Setting Range Default Unit Property
F8-11 Brake release delay 0.200 to 1.500 0.600 s
★
This parameter is used to set the time during which the system retains the zero-speed
torque current output.
Function
Code
Name Setting Range Default Unit Property
F8-12 0 to F6-00 0 -
★
-
Function
Code
Name Setting Range Default Unit Property
F8-14
HCB communication
setting
Bit0: HCB
communication baud
rate
Bit4: Energy saving of
HCB communication
Bit9: Faint light control
of HCB buttons
0 -
☆
F8-15
CAN Communication
setting
Bit10: Door open/close
button not controlled by
the IC card
0 -
☆
F8-16
Start address of hall call
auxiliary command
0 to 40 0 -
★
F8-17 Hall call address check 0 to 1 0 -
★