103
Section 7 Decision-Makerr 6000 ControllerTP-6356 4/12
Section 7 Decision -Makerr 6000 Controller
7.1 General Repair Information
This section contains Decision-Maker 6000 controller
repair information. Service replacement of the
controller is limited to the items shown in Figure 7-1.
Refer to the respective controller parts catalog for
service part numbers. No other replacement service
parts are available.
Before replacing the controller, remove all external
accessories and other electrical connections to verify
that these items are not the cause of the controller
problems. Verify that the accessories and connections
are functioning correctly before reconnecting them to
the new controller.
Electrical noise can affect the controller operation, refer
to Appendix F, Electrical Noise and Wiring Practices.
The controller receives input signals from several
senders/sensors that provide fault warnings and
shutdowns that can be tested for proper function.
Simulating these conditions may be helpful in
troubleshooting the generator set. Refer to Section
8.22, Fault Warning and Shutdown Testing.
Go to Menu 20, Factory Setup and verify that the
application software (code version) is correct for the
generator set model and alternator voltage. Use the
respective controller operation manual for details
regarding Menu 20, Factory Setup.
7.2 SiteTecht Software
The following items are necessary PC requirements for
using the SiteTecht software.
D SiteTecht Software Version 2.0 or higher by
accessing TechTools to download on your PC hard
drive or disk/drive if not already installed on your PC.
D TP-6701 SiteTecht Software Operation Manual
available by accessing TechTools.
D USB Cable with male USB-A and mini-B connectors.
See TP-6701.