10: Remote Power Managers
SLCâ„¢ 8000 Advanced Console Manager User Guide 237
4. Click Apply to Save.
RPMs - Manage Device
The Manage Device page allows the administrator to modify the settings for a managed RPM.
To modify a managed RPM:
1. Click the Devices tab and select the RPMs option. Figure 10-1 Devices > RPMs shows the
page which displays.
2. Select an RPM and click the Manage Device link. Figure 10-8 RPMs - Managed Device
shows the page which displays.
Critical Emails If an email address is specified, under critical conditions (see Critical SNMP
Traps above), an email notification will be sent to the email address. The
Server and Sender configured in the SMTP settings will be used to send the
email.
Low Battery For UPS devices only. Indicates the behavior to take when the UPS reaches a
low battery state. Options are to Shutdown this UPS - shutdown only the
UPS that has reached a low battery state; Shutdown all UPSes - shutdown
all UPSes managed by the SLC; Allow battery failure - allow the battery to
completely fail, which may result in the unsafe shutdown of the devices it
provides power to; Shutdown both SLC UPSes - shutdown both UPSes that
provide power to the SLC, including the UPS with that has reached a low
battery state (some SLCs have dual power supplies). For more information,
see RPM Shutdown Procedure.
Shutdown Order For UPS devices only. If any of the UPSes managed by the SLC reaches a
low battery state AND is configured for Shutdown all UPSes for its Low
Battery setting, this indicates the order in which this UPS will be shutdown. All
UPSes with a shutdown order of "1" will be shutdown first, followed by all
UPSes with a shutdown order of "2", etc. Shutdown orders are in the range of
1 to 49, with 50 being reserved for UPSes that provide power to the SLC -
they will always be shutdown last (see Provides SLC Power below).
Provides SLC Power For UPS devices only. Indicates if this UPS provides power to the SLC.