Table 1. Typical Three-wire Circuit Components
Component
Found On
Shuttle Press
Centrifugal
Extractor
Stop (0) push button on control panel
Emergency Stop switch(es) (locking push button)
Manually lifted access door (typically two per machine)
Manually removed access panel (typically two per machine)
Pull cord (certain shuttles)
Kick plate (typically two per machine)
Test each interlocked machine as follows:
1. Start the machine and place in Manual mode (machine idling in manual).
2. For each three-wire circuit component on the machine:
a. Actuate the component (e.g., press the Stop button) and verify that the machine shuts
down (as indicated by the operator alarm).
b. If needed, de-actuate the component. For example, release an Emergency Stop switch or
close an access door, so the next component can be tested.
For Owner/Management