PARAMETERS
102
4.2.23 Reset selection/disconnected PU detection/PU stop
selection (Pr. 75)
Pr. 75 "reset selection/disconnected PU detection/PU stop selection"
You can select the reset input acceptance, PU (FR-PU04) connector disconnection
detection function and stop function.
!
Reset selection : You can select the reset function input timing.
!
PU disconnection detection :When it is detected that the control panel/PU
(FR-PU04) is disconnected from the inverter for more
than 1 second, the inverter outputs an alarm code
(E.PUE) and comes to an alarm stop.
!
PU stop selection : When an alarm occurs in any operation mode, you can
stop the inverter from the PU by pressing the
STOP
RESET
key.
Parameter Number Factory Setting Setting Range
75 14 0 to 3, 14 to 17
<Setting>
Pr. 75
Setting
Reset Selection
PU Disconnection
Detection
PU Stop Selection
0 Reset input normally enabled.
1
Reset input enabled only when the
protective function is activated.
If the PU is disconnected,
operation will be continued.
2 Reset input normally enabled.
3
Reset input enabled only when the
protective function is activated.
When the PU is
disconnected, an error is
displayed on the PU and
the inverter output is shut
off.
Pressing the
STOP
RESET
key decelerates the
inverter to a stop
only in the PU
operation mode.
14 Reset input normally enabled.
15
Reset input enabled only when the
protective function is activated.
If the PU is disconnected,
operation will be continued.
16 Reset input normally enabled.
17
Reset input enabled only when the
protective function is activated.
When the PU is
disconnected, an error is
displayed on the PU and
the inverter output is shut
off.
Pressing the
STOP
RESET
key decelerates the
inverter to a stop in
either of the PU
and CC-Link
operation modes.