PARAMETERS
104
Pr. 79
"operation mode selection"
Related parameters
4.2.24 Parameter write disable selection (Pr. 77)
Pr. 77 "parameter write disable selection"
You can select between write-enable and disable for parameters. This function is used
to prevent parameter values from being rewritten by incorrect operation.
Parameter
Number
Factory
Setting
Setting Range
77 0 0, 2
<Setting>
Pr. 77 Setting Function
0
Parameter values may only be written while the inverter is at a stop in the
PU or CC-Link operation mode. (Note 1)
2 Write enabled even while the inverter is running.
Note:1. The parameters half-tone screened in the parameter list can be set at any
time.
2. If Pr. 77 = 2, the values of Pr. 23, Pr. 66, Pr. 71, Pr. 79, Pr. 90, Pr. 96,
Pr. 180 to Pr. 183 and Pr. 190 to Pr. 192 cannot be written during operation.
Stop operation when changing their parameter settings.
3. When the parameter unit (FR-PU04) is used, setting "1" in Pr. 77 can inhibit
parameter write. At this time, values may be written to Pr. 75, Pr. 77 and
Pr. 79.
Parameter clear and parameter all clear are also be inhibited.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi FR-E520-0.1KN and is the answer not in the manual?

Mitsubishi FR-E520-0.1KN Specifications

General IconGeneral
BrandMitsubishi
ModelFR-E520-0.1KN
CategoryInverter
LanguageEnglish

Related product manuals