INSTALLATION AND WIRING
40
2.3.5 Peripheral devices
(
1
)
Selection of peripheral devices
Check the capacity of the motor to be used with the inverter you purchased.
Appropriate peripheral devices must be selected according to the capacity.
Refer to the following list and prepare appropriate peripheral devices:
No-Fuse Breaker (NFB) or Earth Leakage
Circuit Breaker (NV)
Magnetic Contactor
(MC)
Inverter Type
Motor
Output
(kW)
Power
Supply
Capacity
(kVA)
Standard
With power factor
improving reactor
ABC
FR-E520-0.1KN 0.1 0.4 Type NF30, NV30 5A Type NF30, NV30 5A S-N11 S-N18 S-N20
FR-E520-0.2KN 0.2 0.8 Type NF30, NV30 5A Type NF30, NV30 5A S-N18 S-N20 S-N20
FR-E520-0.4KN 0.4 1.5 Type NF30, NV30 5A Type NF30, NV30 5A S-N18 S-N21 S-N21
FR-E520-0.75KN 0.75 2.5 Type NF30, NV30 10A Type NF30, NV30 10A S-N18 S-N21 S-N21
FR-E520-1.5KN 1.5 4.5 Type NF30, NV30 15A Type NF30, NV30 15A S-N21 S-N25 S-N50
FR-E520-2.2KN 2.2 5.5 Type NF30, NV30 20A Type NF30, NV30 15A S-N11,S-N12
FR-E520-3.7KN 3.7 9 Type NF30, NV30 30A Type NF30, NV30 30A S-N20
FR-E520-5.5KN 5.5 12 Type NF50, NV50 50A Type NF50, NV50 40A S-N25
Three-phase 200V
FR-E520-7.5KN 7.5 17
Type NF100, NV100
60A
Type NF50, NV50 50A S-N35
Note:1. Select the type of the no-fuse
breaker in (NFB) response to
the power supply capacity.
2. The power supply cable size
of the motor indicated
assumes that its length is
20m.
3. The inverter input side
magnetic contactor to be
chosen differs between the
applicable ranges A, B and C
shown on the right,
depending on the power
supply capacity and wiring
Wiring length(m)
C
BA
Power factor
improving
AC reactor
range
50
500
Power supply capacity(kVA)
01020
Note: Power supply used has the above
recommended size.
len
g
th. For the FR-E520-0.4KN to 1.5KN, choose the S-N10 when the
power factor improving reactor (FR-BEL or FR-BAL) is used.
4. When the inverter capacit
y
is
g
reater than the motor capacit
y
, choose the
breaker and ma
g
netic contactor in accordance with the inverter t
y
pe and
choose the cables and power factor improvin
g
reactor in accordance with
the motor output.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi FR-E520-0.1KN and is the answer not in the manual?

Mitsubishi FR-E520-0.1KN Specifications

General IconGeneral
BrandMitsubishi
ModelFR-E520-0.1KN
CategoryInverter
LanguageEnglish

Related product manuals