Operating 15088:K 3/21/01 2-23
Section 4.1 Acknowledging a Fire Alarm
To acknowledge a fire alarm condition at the panel:
ACK
STEP
Push
and the ALARM: device status will change to
ACK AL (
Acknowledged Fire Alarm).
When the fire alarm condition clears (either automatically in the case of devices programmed for
Tracking
, or
by depression of the
SYSTEM RESET
key), the panel will display CLR AL and the piezo will resound. To
acknowledge the clearing of a fire alarm:
ACK
STEP
Push
and the CLR AL status will change to
ACL AL
(Acknowledged Clear Fire Alarm).
When multiple events have occurred, the system will display the first event that occurred (with the exception
that the first fire alarm will always override any previous trouble). When the ACK STEP key is pushed, the
operator will have acknowledged the highest priority event,
not necessarily the event that is being displayed
on the CRT Monitor and DIA. The acknowledged message for the first prioritized event will be displayed for
several seconds, followed by display of the next priority unacknowledged event.
NOTES
• The piezo sounder will be silenced only after all events have been acknowledged.
• Security alarms are treated like fire trouble conditions in the AM2020/AFP1010.
• Reset the system using the System Reset Key after all alarms have been investi-
gated and subsequently cleared.
• Alarm signals from devices not selected for tracking need a system reset in order
to clear.
For an AM2020/AFP1010 panel on the NOTI•FIRE•NET system, acknowledgment of any event may be
accomplished from the local fire alarm panel, intelligent network annunciator (INA), or network reporting
terminal (NRT). Acknowledging alarms and events from any of these locations automatically provides
acknowledgment at all locations. Fire alarm signals are acknowledged individually at the local fire alarm
panel, NRT, or INA. If the same event on the same point occurs on multiple nodes, the event on the node with
the lowest node address has the highest priority. For more information on priorities and acknowledging events
on the NOTI•FIRE•NET system, refer to the INA Manual, Document 15092, or the NRT Manual, Document
15090.

Table of Contents

Other manuals for Notifier AFP1010

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Notifier AFP1010 and is the answer not in the manual?

Notifier AFP1010 Specifications

General IconGeneral
BrandNotifier
ModelAFP1010
CategoryFire Alarms
LanguageEnglish

Related product manuals