1-8
Installation 15088:K 3/21/01
Mounting
Holes
Figure 2.1-1 Cabinet Backbox Mount
Section 2.1 Mounting the Backbox
The cabinet may be either surface mounted or semi-flush mounted (refer to Figure 2.1-1). Mount the cabinet in
a clean, dry, vibration-free area, using the four holes provided in the back surface of the backbox. Locate the
cabinet so that the top edge is 66 inches (168 cm) above the surface of the finished floor. This procedure places
the center of the control panel keypad 60 inches (152 cm) above the finished floor.
CAUTION!
Unless you are familiar with the placement of components within this backbox, use only the knockout
locations provided for conduit entry. Do not allow any conduit entry at the bottom of the panel where the
batteries are to be mounted (see Figure 2.4-2).