Programming 15088:K 3/21/01
3-9
Section 1.1 Partial System Programming
D }X1X
1=PSYS
Option 1 from the Main Programming menu allows the programmer to change the programming of system-
wide functions such as Alarm Verification of detectors, Signal-Silence Inhibit, Signal Cut-out, disabling the
piezo sounder, enabling Rapid Polling, and enabling supervision of peripheral equipment in the system.
Additional system parameters, such as the number of APS-6R, LIBs, Annunciators and ISIB in the system. The
LIB SLC Loops can also be changed in Partial System Programming.
After selecting option 1 from the Main Programming menu, the display will show the Partial System
Programming submenu:
PRESS@1=INST,2=STY,3=TDLY,4=AVPS,5=ZBND,6=EXTEQ,7=LOCP,8=ISIB,9=PARM@@@@@@@@@:
NOTE: Submenu option 4 includes APS-6R as well as AVPS power supplies.
The Partial System Programming submenu has nine options, where:
1=INST Installation - Installation or removal of the Loop Interface Boards from memory.
2=STY Style - Changing (in memory) the NFPA style of the SLC Loops.
3=TDLY Time Delays - Setting the time delays for Alarm Verification, Signal-Silence Inhibit,
and Signal Cut-Out.
4=AVPS Audio/Visual Power Supplies - Telling the AM2020/AFP1010 how many Audio/Visual
Power Supplies and APS-6R Auxiliary Power Supplies are installed in the system.
5=ZBND Zone Boundary - Setting the zone boundary for the software memory map.
6=EXTEQ External Equipment - Changing the external equipment options, such as electrical
supervision of the CRT Monitor.
7=LOCP Local Parameters - Setting local parameters, such as enabling or disabling the piezo
sounder during point programming of SLC Loop devices, LIB Local Mode and NFPA pro-
gramming.
8=ISIB Intelligent Serial Interface Board - Installation or removal of the Intelligent Serial In-
terface Board (SIB-2048A or SIB-NET) or annunciator modules (see Chapter One,
Serial Communications
, for a description of annunciator modules). Also used to en-
able the external interface for upload/download, and Universal Digital Alarm Commu-
nicator Transmitter selection.
9=PARM Additional System Parameters - Selection of additional system parameters such as
the detector day/night sensitivity settings, rapid polling, etc.
The Partial System Programming Menu flow chart is located in Figure 1-2. Detailed information on the Partial
System Programming options follows.
NOTES
When removing loop interface boards, all installed points on the affected LIBs are automatically
removed upon cycling power to the system. Programming information for installed points can be
stored in a VeriFire™ database prior to removal of the LIB. Use of the VeriFire™ application for
the reprogramming of previously removed points is highly recommended.
When removing annunciator modules, all installed points on the affected annunciators must be removed
first for proper system operation.