3-46
Programming 15088:K 3/21/01
Section 2.5 Diagnostics C |X5X
5=DIAG
Option 5 from the Alter Status Menu allows the programmer to perform system diagnostics.
The Diagnostics Option submenu is shown below:
PRESS@1=RVER@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@:@@
1=RVER - Reset Detector Verification Counters C |X5X1X
This option allows the programmer to reset the detector verification counters for all installed intelligent detectors
and clear all detector verification error conditions.
The detector verification counter associated with each detector indicates how many times that detector has en-
tered the alarm verification routine without producing a valid fire alarm.
The following example illustrates the execution of this option:
PRESS@1=RVER@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@:@1
DO@YOU@WANT@TO@RESET@THE@DETECTOR@VERIFICATION@COUNTERS?@(Y=YES,N=NO)@@@@@@@@:@Y
Section 2.6 Walk Test C |X6X
6=WALK
Option 6 from the Alter Status Menu allows the programmer to select which LIBs will participate in walk test.
Upon completion of walk test, the programmer will be able to choose from the optional walk test reports.
After Selecting option 6 from the Alter Status menu, the display will show the Walk Test submenu:
PRESS@1=SEL,2=UNP,3=UNI,4=TEST,5=UNTST,6=EXIT@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@:
The Walk Test submenu has six options, where:
1=SEL Select - Select which LIB boards will participate in Walk Test.
2=UNP Unprogrammed Device Report - Allows the programmer to generate a report for un-
programmed devices in the area designated for Walk Test that are connected to the SLC
but not defined in the panel database.
3=UNI Uninstalled Device Report - Allows the programmer to generate a report for
uninstalled devices in the area designated for Walk Test that have been defined in the
panel data base but not physically installed on the SLC.
4=TEST Tested Devices Report - Allows the programmer to generate a report for tested de-
vices in the area designated for Walk Test.
5=UNTST Untested Device Report - Allows the programmer to generate a report for untested
devices in the area designated for Walk Test.
6=EXIT Exit Walk Test - Allows the programmer to exit/abort the Walk Test Mode.

Table of Contents

Other manuals for Notifier AFP1010

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Notifier AFP1010 and is the answer not in the manual?

Notifier AFP1010 Specifications

General IconGeneral
BrandNotifier
ModelAFP1010
CategoryFire Alarms
LanguageEnglish

Related product manuals