Appendix E: Detector Initialization How to Manually Initialize a Detector
102
NFS-640 Programming Manual P/N 51333:B 10/03/2003
How to Manually Initialize a Detector
You only need to manually initialize a detector when you change a detector during Walk Test or
Advanced Walk Test. If, however, you replace a detector with a different type of detector, you must
immediately program the new detector according to the instructions in “How to Replace a Detector” on
page 101.
To manually initialize a detector, follow these steps:
1. Press the
ENTER key. The control panel displays the Program Entry screen:
2. Press the 1 key. The control panel displays the Enter Password screen:
3. Enter the password
RESET, which starts detector initialization. The control panel displays the
following three screens, in the sequence shown, while initializing a detector:
When the control panel completes the detector initialization, it displays system status as shown below:
1=PROGRAMMING 2=READ STATUS ENTRY
(ESCAPE TO ABORT)
ENTER PROG OR STAT PASSWORD, THEN ENTER.
(ESCAPE TO ABORT)
Detector Initializing _ Please Wait
02:48P 071401 Sat
CHECKING MEMORY NFS-640 Release 1.0
Software #XXXXXXX
SYSTEM NORMAL 02:50P 071401 Sat
www.PDF-Zoo.com