How to Use the Basic Program 2. Program Change
NFS-640 Programming Manual P/N 51333:B 10/03/2003 41
How to Check the Program for Errors (8=CHECK PRG)
When finished programming, you can use the Check option to search the program
entries for possible errors. From the “Basic Program” screen, press the 8 key. The
Check option searches the program for the following conditions that can cause
errors:
Output points mapped to a zone without a mapped input
A zone with mapped input points without mapped output points (including Z00 outputs)
Releasing zone inputs (R0-R9) with no
RELEASE CKT outputs mapped to them; or RELEASE CKT
outputs with no R0-R9 inputs mapped to them
RO-R9 inputs not mapped to
MAN. RELEASE.
Note: For more information on Releasing Zone, refer to “Appendix A: Releasing Applications” on page 53.
If the Check option detects multiple devices that fail the check, press the PREVIOUS or NEXT key to step
through the devices. If the Check option displays errors, return to Point Programming (“How to Modify
or Delete a Point (2=point)” on page 21) and correct the errors. The figure below shows a sample
display of program screen that appears after a successful program check:
Program Change
Password
PROGRAM CHECK OK.
RE-TEST PANEL NOW 08:34A 110700 Tue
www.PDF-Zoo.com

Table of Contents

Other manuals for Notifier NFS-640

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Notifier NFS-640 and is the answer not in the manual?

Notifier NFS-640 Specifications

General IconGeneral
BrandNotifier
ModelNFS-640
CategoryFire Alarms
LanguageEnglish

Related product manuals