2. Program Change How to Use the Basic Program
32
NFS-640 Programming Manual P/N 51333:B 10/03/2003
How to Change Global System Functions (7=SYSTEM)
The System option lets you select settings for global system functions that apply
to all programmed devices and zones. For instance, selecting an Alarm
Verification Timer for 30 seconds means that all initiating devices selected for
Alarm Verification use a 30-second timer. From the “Basic Program” screen,
press the 7 key to display the “System Function” screen as shown below:
Global System Functions
Settings for global system functions:
Table 11 Settings for Global Systems Functions
System Function Setting Default
SIL INH (Silence Inhibit Timer) 0 to 300 seconds 000
AUTO (Auto Silence Timer) - After the time
delay expires, functions like pressing the
SIGNAL SILENCE key, silencing active
outputs programmed as silenceable.
000 (none); 600 to 900 seconds 000
VERIFY (Alarm Verification Timer) 0 to 60 seconds* 60
USA TIME
USA time (mm/dd/yy) or
EUR time (dd/mm/yy)
Press the
NEXT or PREVIOUS key to change.
Note that (European) time changes to
24-hour time format and date format.
USA
TERM - Allows supervision for devices
connected to TB12, i.e., LCD-80.
N = no supervision
Y = supervision enabled
N
AC_DLY AC delay – delays loss of AC reporting for
8 hours.
Y=AC delay; N=no AC delay
Y
LocX - One of three operating modes of PC or
terminal connected to the control panel
through TB15 on the CPU-640.
Note: For a complete list of functions, refer to
the NFS-640 Operations Manual.
LocT -(terminal connected to control
panel and located in same room).
LocM -(same as LocT but requires
password).
RemT -(terminal connected through a
modem for Read Status only).
LocT
BLINK - Addressable SLC device LED blink. Select from 00 to 16.
(00 = no blink, 01 = blink every poll, 02 =
blink every 2nd poll, 03 = blink every 3rd
poll up to 16 = blink every 16th poll).
Note: This setting affects FlashScan
modules only.
01
ST - The NFPA wiring style used for the SLC. 6=Style 6 SLC wiring
4=Style 4 SLC wiring
4
ACS - Use ACS Selection Groups (Refer to
“Annunciator Options” on page 33).
N or Y N
*This value can not exceed 30 seconds for ULC installations.
Program Change
Password
SIL INH=000 AUTO=000 VERIFY=30 USA TIME
TERM=N AC_DLY=Y LocT BLINK=01 ST=4 ACS=N
www.PDF-Zoo.com

Table of Contents

Other manuals for Notifier NFS-640

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Notifier NFS-640 and is the answer not in the manual?

Notifier NFS-640 Specifications

General IconGeneral
BrandNotifier
ModelNFS-640
CategoryFire Alarms
LanguageEnglish

Related product manuals