How to Program a Releasing Zone Appendix A: Releasing Applications
NFS-640 Programming Manual P/N 51333:B 10/03/2003 71
How to Program a Release End Bell Circuit
Note: A releasing circuit with this Type Code requires the following selections: A Releasing Zone selection (R0-R9);
An output circuit mapped to the same Releasing Zone; Switch Inhibit selected; Non-Silenceable; No Walk Test.
The following contains information needed to program a Release End Bell circuit for a control module
a NAC or a Panel Circuit
.
Description A control module, NAC, or Panel Circuit to activate an audible or visual device when
releasing devices shut off. You can also program multiple outputs with the
REL END
BELL Type Code to the same Releasing Zone. When all the Releasing Zone functions
are complete, all outputs with the
REL END BELL Type Code activate at the same time.
A
REL END BELL circuit remains on until you reset the system.
How to
program
1. Select a control module, NAC or Panel Circuit (refer to “How To Modify Or
Delete A Point (2=
POINT)” on page 21) that you want to use as a Release End
Bell circuit.
2. Select the
REL END BELL Type Code, as shown in the following example
(control module shown).
3. Select the Releasing Zone (R0-R9) for your releasing application.
4. Press the
ENTER key to save, then press the ESC key two times to return to the
Program Change screen.
Example
A programming example of a control module programmed as a Release End Bell for
Releasing Zone R5.
Figure 16 Control Module Configured as a Release End Bell Circuit
Type Code selection: REL END BELL
Releasing Zone
selection (R5 shown)
Walk Test
Selection: * = off
PROGRM REL END BELL MODULE ADDR 2M108
R5 __ __ __ __ I** 2M108
Switch Inhibit: I = selected
Silenceable: * = off
Type Code
REL END BELL
Type Code
REL CIRCUIT
Type Code
REL CIRCUIT
Type Code
REL AUDIBLE
For example, a control module programmed with the REL END
BELL Type Code activates when all releasing functions, such
as the releasing functions programmed for R05 shut off.
Control
Module
B02
B01
Control
Module
R05
Monitor
Module
Detector
Detector
Detector
Xzone4.cdr