How to Program a Releasing Zone Appendix A: Releasing Applications
NFS-640 Programming Manual P/N 51333:B 10/03/2003 75
How to Program a Release Audible Circuit
Note: An output with a REL AUDIBLE Type Code requires the following selections: A Releasing Zone selection (R0-R9);
An output circuit mapped to the same Releasing Zone; Switch Inhibit selected; Non-Silenceable; No Walk Test.
The following contains information needed to program a Release Audible circuit for an output circuit
(control module, NAC, or Panel Circuit)
.
Description An output circuit programmed to activate an audio or visual device when all
releasing outputs, programmed to the same Releasing Zone, turn on. You can also
program multiple outputs with the
REL AUDIBLE Type Code to the same Releasing
Zone. When the Releasing Zone activates, all outputs with the
REL AUDIBLE Type
Code activate at the same time.
How to
program
1. Select a control module, NAC, or Panel Circuit (refer to “How To Modify Or
Delete A Point (2=
POINT)” on page 21) that you want to use as a Releasing Circuit.
2. Select the
REL AUDIBLE Type Code, as shown in the following example
(control module shown).
3. Select the Releasing Zone (R0-R9) for your releasing application.
4. Press the
ENTER key to save, then press the ESC key two times to return to the
Program Change screen.
Example
A programming example of a control module programmed as a Release Audible circuit for
Releasing Zone R5.
Figure 20 Control Module Configured as a Release Audible Circuit
Type Code selection: REL AUDIBLE
PROGRM REL AUDIBLE MODULE ADDR 2M108
R5 __ __ __ __ I** 2M108
Releasing Zone
selection (R5 shown)
Walk Test
Selection: * = off
Silenceable: * = off
Switch Inhibit: I = selected
Type Code
REL AUDIBLE
Type Code
REL CIRCUIT
Type Code
REL CIRCUIT
Type Code
REL AUDIBLE
For example, a control module programmed with the REL
AUDIBLE Type Code activates simultaneously with other
outputs programmed for R05 (B01 and B02).
Control
Module
B02
B01
Control
Module
R05
Monitor
Module
Detector
Detector
Detector
Xzone4.cdr
www.PDF-Zoo.com

Table of Contents

Other manuals for Notifier NFS-640

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Notifier NFS-640 and is the answer not in the manual?

Notifier NFS-640 Specifications

General IconGeneral
BrandNotifier
ModelNFS-640
CategoryFire Alarms
LanguageEnglish

Related product manuals