How to Program a Releasing Zone Appendix A: Releasing Applications
NFS-640 Programming Manual P/N 51333:B 10/03/2003 73
How to Program a Release Circuit for an Output Circuit
Note: A Release Circuit with this Type Code requires the following selections: A Releasing Zone selection (R0-R9);
An output circuit mapped to the same Releasing Zone; Switch Inhibit selected; Non-Silenceable; No Walk Test.
Note: Do not use a Release Circuit for the following: An application requiring ULC Listing; An application requiring
power-limited energy cable.
The following contains information needed to program a Release Circuit for an output circuit (control
module or NAC)
.
Description A control module or a NAC used to activate a releasing solenoid or other releasing
device. You can also program multiple outputs with the
RELEASE CKT Type Code to
the same Releasing Zone. When the Releasing Zone activates, all outputs associated
with the releasing zone and with the
RELEASE CKT Type Code also activate at the
same time. A Release Circuit activates when:
An initiating device programmed to the same Releasing Zone activates (two
devices if using the Cross Zone option)
The Delay Timer for R0-R9 (if used) expires
The Abort Switch for R0-R9 (if used) is not active
How to
program
1. Select a control module or a NAC (refer to “How to Modify or Delete a Point
(2=
POINT)” on page 21) that you want to use as a Release Circuit.
2. Select the
RELEASE CKT Type Code, as shown in the following example (control
module shown).
3. Select the Releasing Zone (R0-R9) for your releasing application.
4. Press the
ENTER key to save, then press the ESC key two times to return to the
Program Change screen.
Example
A programming example of a control module programmed as a Release Circuit for Releasing
Zone R5.
Figure 18 Control Module Configured as a Release Circuit
Type Code selection: RELEASE CKT
Releasing Zone
selection (R5 shown)
PROGRM RELEASE CKT MODULE ADDR 2M108
R5 __ __ __ __ I** 2M108
Walk Test
Selection: * = off
Silenceable: * = off
Switch Inhibit: I = selected
Type Code
REL CIRCUIT
Control
Module
B02
B01
Control
Module
R05
Monitor
Module
Detector
Detector
Detector
Xzone4.cdr
Type Code
REL CIRCUIT
For example, all control modules programmed with the REL
CIRCUIT Type Code activate simultaneously with other outputs
programmed for R5 (B01, B02).
www.PDF-Zoo.com

Table of Contents

Other manuals for Notifier NFS-640

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Notifier NFS-640 and is the answer not in the manual?

Notifier NFS-640 Specifications

General IconGeneral
BrandNotifier
ModelNFS-640
CategoryFire Alarms
LanguageEnglish

Related product manuals