Appendix A: Releasing Applications How to Program a Releasing Zone
56
NFS-640 Programming Manual P/N 51333:B 10/03/2003
Programming a ULI Abort Switch
The following contains information needed to program a ULI Abort Switch:
Description A standard UL-type delay timer that complies with UL Standard 864.
How to program 1. Program the monitor module connected to the abort station with the Type Code
ABORT SWITCH as detailed in “How to Modify an Addressable Monitor Module
Point” on page 23.
2. Select a time for the Releasing Zone Delay Timer (refer to“How to Program a
Delay Timer” on page 54).
3. Press at this point to save the Abort Switch value if no other fields on the
screen are changing. To change another field on the screen, move the cursor into
position by pressing the arrow keys on the keypad.
How it works
When an alarm initiates in the programmed Releasing Zone, you can press and hold the Abort
Switch while the Delay Timer continues to count down. (If the delay timer has expired, the abort
switch has no effect.) When you release the Abort Switch, a 10-second ULI timer counts down.
At the end of the 10-second ULI timer, the control panel activates the Releasing Zone outputs.
Example
A ULI Abort Switch and a Delay Timer programmed to Releasing Zone R05:
Figure 6 ULI Abort Switch Example
To Program Do this
ULI Abort Switch Type ULI in the ABORT= field, or press the
NEXT or PREVIOUS
keys: or until ULI appears in the field.
Release the Abort
Switch; the 10-second
ULI timer begins
Delay=15 sec.
Press and hold the
Abort Switch for 15
seconds
15 sec.
When the 10-seconds
ULI timer expires, the
control panel activates
Releasing Zone outputs
10 sec
Program selections for Releasing Zone R05
5 sec.
Total time from alarm initiation to release:
5 + 15 + 10 = 30 seconds
Alarm
0 sec.
5 sec.
15 sec.
20 sec.
30 sec.
PRG RELEASE FUNCT RELEASE CONTROL
DELAY=15 ABORT=ULI CROSS=N SOK=0000 R05
www.PDF-Zoo.com