EasyManuals Logo
Home>Notifier>Fire Alarms>NFS-640

Notifier NFS-640 Programming Manual

Notifier NFS-640
116 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #51 background imageLoading...
Page #51 background image
How to Do a Walk Test 3. Status Change
NFS-640 Programming Manual P/N 51333:B 10/03/2003 51
Operate the control panel in Walk Test as follows
Basic Walk Test directs the control panel to do the following:
Activate silenceable outputs associated by programming with each new alarm. (The panel does
not activate non-silenceable outputs.)
Save and store each test in the History buffer
Send a TEST Axx status banner for each alarm, and a TEST TXX banner for each trouble, to
the printer (xx equals the number of tests for a detector or input device with this address)
Turn on the System Trouble LED
Turn on the System Trouble relay
Disable activation of the System Alarm relay
Advanced Walk Test
During Advanced Walk Test, when the tester activates an input, all CBE mapped to that input will
activate with the exception of releasing functions. Each input activation is latching; that is, it will not
deactivate until the system is reset. Advanced Walk Test will sound all activated outputs, overriding a
setting of “
*” (silent) in the Walk Test field.
Note: Some detectors, laser detectors for example, can be difficult to place in alarm using a magnet. Advanced Walk
Test facilitates magnet testing of these detectors.
Enter Advanced Walk Test as follows:
Enter LTEST at the password screen. Asterisks will display where LTEST has been
typed. Pressing
ENTER displays the following screen.
Note: The control panel cannot be put into Walk Test from an alarm condition.
Advanced Walk Test directs the control panel to do the same as it does for Basic Walk Test (see “Basic
Walk Test” above) with the following exceptions:
alarm and trouble messages are sent to the printer, not test messages. (These Walk Test
messages can be distinguished from others at the printer because they begin with the trouble
message generated when Walk Test is entered, and end with the cleared trouble when Walk
Test is exited.)
all CBE mapped to the test input is activated except releasing functions.
Walk Test Activation Indications
Walk Test Activation Indications
FlashScan poll mode - Once the test is started:
•each intelligent addressable input device will blink its address in red, and each intelligent
addressable output device will blink its address in green. Pattern examples are given below.
To Press
Put the control panel into Walk Test mode
Stop a Walk Test and return to the “Status Change Selection” screen
To P re s s
Stop an Advanced Walk Test and return to
the “Status Change Selection” screen
Address Blink Pattern
8 8 blinks, long stop, 8 blinks, long stop,....
LTEST
TROUBL IN SYSTEM ADV WALK TEST
PROCESSING DISABLED 10:07a 051903 MON
www.PDF-Zoo.com

Table of Contents

Other manuals for Notifier NFS-640

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Notifier NFS-640 and is the answer not in the manual?

Notifier NFS-640 Specifications

General IconGeneral
BrandNotifier
ModelNFS-640
CategoryFire Alarms
LanguageEnglish

Related product manuals