2. Program Change How to Use the Basic Program
16
NFS-640 Programming Manual P/N 51333:B 10/03/2003
How to Clear Memory (0=CLR)
The Clear option removes all programming information from control panel
memory. If installing the control panel for the first time, use option 0 to clear
control panel memory. To do so, follow these steps:
1. From the “Basic Program” screen, press the 0 (zero) key to display the Clear Program screen. The
control panel prompts for verification as shown below:
2. Press the
ENTER key to clear control panel memory or press the ESC key to exit the screen without
clearing.
How to Autoprogram the Control Panel (1=AUTO)
Purpose
The Autoprogram option identifies all addressable devices connected to the control panel. Devices
include addressable detectors and modules connected to SLC 1 or SLC 2, Panel Circuits connected to J5
and J6, and NACs. You can use the Autoprogram option to create a new program and add or remove
devices. A summary of the Autoprogram functions, when to use the functions, and where to find
information on using the functions is found below:
Autoprogram Function Control Panel Configuration Refer to...
Create a new program for
the control panel
A new control panel or a control panel with
no existing program in memory.
“Create a New Program for the
Control Panel” on page 17
Add one or more
SLC-connected detectors
and modules to an
existing program
A program exists in memory and you want to
add a detector or module to the existing
program—without modifying information
for existing detectors and modules.
“How to Add a Device to the
Program” on page 18
Remove one or more
SLC-connected detectors
and modules from an
existing program
A program exists in memory and you want to
remove an installed detector or module from
the existing program—without modifying
information for existing detectors and
modules.
“How to Remove a Device from
the Program” on page 18
View system defaults A program exists in memory and you want to
view system settings assigned during
Autoprogram, such as custom labels,
passwords, and so on.
“How to Change Autoprogram
Default Values” on page 20
Program Change
Password
PRESS ENTER TO CLEAR ENTIRE PROGRAM
OR ESCAPE TO ABORT
www.PDF-Zoo.com

Table of Contents

Other manuals for Notifier NFS-640

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Notifier NFS-640 and is the answer not in the manual?

Notifier NFS-640 Specifications

General IconGeneral
BrandNotifier
ModelNFS-640
CategoryFire Alarms
LanguageEnglish

Related product manuals