A - 23
Appendices
NX-series EtherNet/IP Coupler Unit Users Manual (W536)
A-1 Supported CIP Objects
A
A-1-4 TCP/IP Interface Object (Class ID: F5 Hex)
Attribute ID
(hex)
Parameter name Description Attribute Data type Value (hex)
01 Interface Configu-
ration Status
Interface IP address setting
condition
Read DWORD See below.
02 Configuration
Capability
Controller configuration and
settings that are possible for
the interface
Read DWORD See below.
03
*1
*1. The new settings are enabled after the power supply is cycled.
Configuration Con-
trol
IP address setting method
when interface started
Read or
Write
DWORD See below.
04 Physical Link
Object
Path to physical link object Read STRUCT
Path size Path size in words Read UINT 0002 (fixed)
Path Fixed path to physical link
object
Read Padded
EPATH
20F62401 (fixed)
05
*1
Interface Configu-
ration
Interface settings Read or
Write
STRUCT
*2
*2. This indicates the following: 192.168.250.1, 255.255.255.0, 0.0.0.0, 0.0.0.0, 0.0.0.0, “”.
IP Address IP address UDINT C0A8FA01
(fixed)
Network Mask Subnet mask UDINT FFFFFF00
(fixed)
Gateway
Address
Default gateway UDINT 00000000 (fixed)
Name Server Primary name server UDINT 00000000 (fixed)
Name Server 2 Secondary name server UDINT 00000000 (fixed)
Domain Name Domain name STRING 0000 (fixed)
06 Host Name Host name Read or
Write
STRING 0000 (fixed)
0D Encapsulation
Inactivity Timeout
Encapsulation inactivity tim-
eout time
Read or
Write
UINT 0000: Disabled
0000 to 0E10:
Timeout time (s)
Default: 0078
64 NTP server
IP address
NTP server IP address Read or
Write
SHORT_S
TRING
*3
*3. The maximum number of characters is 64.
0: NTP client dis-
abled.
Not 0: IP
address of NTP
server
Default: “0”
66 Time zone Time zone Read or
Write
UINT See below.
Default: 000F
69 TCP/UDP Mes-
sage Service
Server Port No.
TCP/UDP message service
server port number
Read or
Write
UINT
0400 to FFFF
*4
Default: FA00
*4. This is 1,024 to 65,535 decimal. You cannot set 8AE or AF12.

Table of Contents

Other manuals for Omron CJ2-CPU

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron CJ2-CPU and is the answer not in the manual?

Omron CJ2-CPU Specifications

General IconGeneral
BrandOmron
ModelCJ2-CPU
CategoryController
LanguageEnglish

Related product manuals