5 Designing the Power Supply System
5 - 6
NX-series EtherNet/IP Coupler Unit User’s Manual (W536)
5-2 Designing the NX Unit Power Supply
System
This section describes how to design the NX Unit power supply to the EtherNet/IP Slave Terminal.
The total power consumption from the NX Unit power supply must not exceed the NX Unit power supply
capacity of the Unit that supplies the NX Unit power.
Use the following procedure to design the NX Unit power supply.
1 Calculate the total power consumption from the NX Unit power supply that is required by the NX
Units that are connected to the EtherNet/IP Coupler Unit.
2 If the total power consumption from the NX Unit power supply exceeds the NX Unit power sup-
ply capacity of the EtherNet/IP Coupler Unit, add an Additional NX Unit Power Supply Unit to the
right of an NX Unit before the capacity is exceeded.
3 Calculate the total power consumption from the NX Unit power supply that is required by the NX
Units that are connected after the Additional NX Unit Power Supply Unit.
If the total power consumption of those NX Units exceeds the NX Unit power supply capacity of
the Additional NX Unit Power Supply Unit, add another Additional NX Unit Power Supply Unit to
the right of an NX Unit before the capacity is exceeded.
4 Repeat step 3 until the design conditions for the NX Unit power supply are met.
5-2-1 Procedure for Designing the NX Unit Power Supply System
Unit power
supply
Internal power supply circuits
Additional NX Unit Power Supply Unit
Unit power
supply terminals
End Cover
NX Unit power supply
The total power consumption from the
NX Unit power supply must not exceed
the NX Unit power supply capacity.
The total power consumption from the
NX Unit power supply must not exceed
the NX Unit power supply capacity.
NX Units connected to the
EtherNet/IP Coupler Unit
NX Units connected to the Additional
NX Unit Power Supply Unit
NX Unit power supply
Unit power
supply terminals
EtherNet/IP
Coupler Unit

Table of Contents

Other manuals for Omron CJ2-CPU

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron CJ2-CPU and is the answer not in the manual?

Omron CJ2-CPU Specifications

General IconGeneral
BrandOmron
ModelCJ2-CPU
CategoryController
LanguageEnglish

Related product manuals