5
PC Setup Section 1-1
DM 6616 00 to 07 Servicing Time for RS-232C Port (when bits 08 to 15 are set to 01)
00 to 99 (BCD): Percentage of cycle time used to service RS-232C port. The servicing
time must be between 0.256 ms and 65.536 ms.
13
08 to 15 RS-232C Port Servicing Setting Enable
00: 5% of the cycle time
01: Use time in 00 to 07.
(When the PC is stopped, the servicing time will always be 10 ms.)
DM 6617 00 to 07 Servicing Time for Peripheral Port (when bits 08 to 15 are set to 01)
00 to 99 (BCD): Percentage of cycle time used to service peripheral port. The servicing
time must be between 0.256 ms and 65.536 ms.
14
08 to 15 Peripheral Port Servicing Setting Enable
00: 5% of the cycle time
01: Use time setting in bits 00 to 07.
(When the PC is stopped, the servicing time will always be 10 ms.)
DM 6618 00 to 07 Cycle Monitor Time (when bits 08 to 15 are set to 01, 02, or 03)
00 to 99 (BCD) × setting units (See bits 08 to 15.)
17
08 to 15 Cycle Monitor Enable
00: 120 ms (setting in bits 00 to 07 disabled)
01: Setting units: 10 ms
02: Setting units: 100 ms
03: Setting units: 1 s
DM 6619 00 to 15 Cycle Time
0000: Variable (no minimum)
0001 to 9999 (BCD): Minimum cycle time in ms
14
Interrupt Processing (DM 6620 to DM 6639)
The following settings are effective after transfer to the PC the next time operation is started.
DM 6620 00 to 03 Input Time Constant for IR 00000 to IR 00007
0: 8 ms; 1: 1 ms; 2: 2 ms; 3: 4 ms; 4: 8 ms; 5: 16 ms; 6: 32 ms; 7: 64 ms; 8: 128 ms
14
04 to 07 Input Time Constant for IR 00008 to IR 00015 (Setting same as bits 00 to 03)
08 to 11 Input Time Constant for IR 001 (Setting same as bits 00 to 03)
12 to 15 Not used. Set to 0.
DM 6621 00 to 07 Input Constant for IR 002
00: 8 ms; 01: 1 ms; 02: 2 ms; 03: 4 ms; 04: 8 ms; 05: 16 ms; 06: 32 ms; 07: 64 ms;
08: 128 ms
14
08 to 15 Input Constant for IR 003 (Setting same as for IR 002.)
DM 6622 00 to 07 Input Constant for IR 004 (Setting same as for IR 002.)
08 to 15 Input Constant for IR 005 (Setting same as for IR 002.)
DM 6623 00 to 07 Input Constant for IR 006 (Setting same as for IR 002.)
08 to 15 Input Constant for IR 007 (Setting same as for IR 002.)
DM 6624 00 to 07 Input Constant for IR 008 (Setting same as for IR 002.)
08 to 15 Input Constant for IR 009 (Setting same as for IR 002.)
DM 6625 00 to 07 Input Constant for IR 010 (Setting same as for IR 002.)
08 to 15 Input Constant for IR 011 (Setting same as for IR 002.)
DM 6626 00 to 07 Input Constant for IR 012 (Setting same as for IR 002.)
08 to 15 Input Constant for IR 013 (Setting same as for IR 002.)
DM 6627 00 to 07 Input Constant for IR 014 (Setting same as for IR 002.)
08 to 15 Input Constant for IR 015 (Setting same as for IR 002.)
DM 6628 00 to 03 Interrupt Enable for IR 00000
0: Normal input; 1: Interrupt input in Interrupt Input Mode or Counter Mode
26
04 to 07 Interrupt Enable for IR 00001
0: Normal input; 1: Interrupt input in Interrupt Input Mode or Counter Mode
08 to 11 Interrupt Enable for IR 00002
0: Normal input; 1: Interrupt input in Interrupt Input Mode or Counter Mode
12 to 15 Interrupt Enable for IR 00003
0: Normal input; 1: Interrupt input in Interrupt Input Mode or Counter Mode
Word(s) Bit(s) Function Page

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron CQM1H - PROGRAM and is the answer not in the manual?

Omron CQM1H - PROGRAM Specifications

General IconGeneral
BrandOmron
ModelCQM1H - PROGRAM
CategoryController
LanguageEnglish

Related product manuals