5 Advanced Operations
5 - 22
E5@C-T Digital Temperature Controllers User’s Manual (H185)
z Setting Example
In this example, the SP Mode parameter in the Adjustment Level is set to mask (mask (hide)).
Operating Procedure
z Moving to Parameter Mask Mode (Advanced Function Setting Level)
1
Press the M Key several times in the Advanced Function
Setting Level to display the Parameter Mask Setting
parameter.
Advanced Function Setting
Level
2
Press the
U
or
D
Key to set
on
(move to Parameter Mask
Mode).
The default is off.
Refer to 4-1-6 Moving to the Advanced Function Setting Level for the procedure to enter the
Advanced Function Setting Level.
z Hiding the SP Mode Parameter (Adjustment Level)
1
Press the M Key several times in the Adjustment Level to
select the SP Mode parameter.
Adjustment Level
2
Press the
U
or
D
Key to set
mask
(mask (hide)).
The default is disp.
3
Press the
O
Key for at least 1 second to end Parameter Mask
Mode.
Refer to 4-1-3 Moving to the Adjustment Level for the procedure to enter the Adjustment Level.
z Enabling Parameter Masks (Protect Level)
1
Press the M Key several times in the Protect Level to display
the Parameter Mask Enable parameter.
Protect Level
2
Press the
U
or
D
Key to set
on
(enable).
The default is on.
*The SP Mode parameter is masked (i.e., hidden).
Refer to 4-1-5 Moving to the Protect Level for the procedure to enter the Protect Level.
off
pmst
Parameter Mask
Settings
on
pmst
spmd
SP Mode
disp
mask
spmd
pmsk
Parameter Mask
Enable
on
on
pmsk