5 - 53
5 Advanced Operations
E5@C-T Digital Temperature Controllers User’s Manual (H185)
5-15 Program-related Functions
5
5-15-1 Advance
5-15 Program-related Functions
This section describes the following program-related functions.
• Advance
• Segment Jump
• Hold
• Wait
• Program Repetition
• Program Links
• SP Shift
• Time Signals
• Program End Outputs
• RUN Output
• Stage Outputs
• PV Start
• Standby Operation
• SP Mode Switch
• SP Tracking
• Changing Programs during Operation
• Operations Related to Other Functions
The advance operation moves the program to the start of the next segment.
• An advance operation moves the program forward to the end of the present segment each time the
Advance parameter is set to ON. The Advance parameter turns OFF after the next segment has
been reached.
Note 1 This function cannot be performed with a key operation. Use a segment jump (segment num-
ber) for a key operation.
2 The advance operation cannot be executed at the following times:
During reset status, during standby status, during autotuning, and when the Operation End
Operation parameter is set to Continue.
z Related Parameters
Advancing with an Event Input
5-15-1 Advance
Parameter
name
Display Setting range Default Level
Event Input
Assignment
eV-1
eV-2
eV-3
eV-4
eV-5
eV-6
adv: Advance
Event Input Assignment 1:
rr-1
Event Input Assignment 2:
adv
Event Input Assignment 3 to 6:
none
Initial Setting Level

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron E5AC-T and is the answer not in the manual?

Omron E5AC-T Specifications

General IconGeneral
BrandOmron
ModelE5AC-T
CategoryTemperature Controller
LanguageEnglish

Related product manuals