5 - 23
5 Advanced Operations
E5@C-T Digital Temperature Controllers User’s Manual (H185)
5-8 OR Output of Alarms
5
5-8-1 Integrated Alarm
5-8 OR Output of Alarms
You can use an integrated alarm to output an OR of alarms 1 to 4, the HB alarm, the HS alarm, and the
input error. Set the Integrated Alarm Assignment parameter (alma) and then assign the integrated
alarm (alm) to an auxiliary output or a control output.
z Parameters
5-8-1 Integrated Alarm
Parameter
No. 1
display
Value
No. 2
display
Level
Control Output
Assignment
out1 to
out2
ALM: Integrated alarm (The Integrated
Alarm Assignment parameter must be
set separately.)
alm
Advanced
Function Setting
Level
Auxiliary
Output 1 to 4
Assignment
sub1 to
sub4
ALM: Integrated alarm (The Integrated
Alarm Assignment parameter must be
set separately.)
alm
Advanced
Function Setting
Level
Integrated
Alarm
Assignment
alma
Set the sum of the following values for
the alarms and errors to include in the
OR output. 0 to 255
Alarm 1: +1
Alarm 2: +2
Alarm 3: +4
Alarm 4: +8
HB alarm: +16
HS alarm: +32
Input error: +64
Not used.: +128
(Default: 49 (i.e., an OR of alarm 1, the
HB alarm, and the HS alarm))
0 to 255
Advanced
Function Setting
Level