A - 37
A Appendices
E5@C-T Digital Temperature Controllers User’s Manual (H185)
A-8 Setting Levels Diagram
A
A-8 Setting Levels Diagram
This diagram shows all of the setting levels. To move to the Advanced Function Setting Level and Cali-
bration Level, you must enter passwords. Some parameters are not displayed depending on the protect
level setting and the conditions of use.
Control stops when you move from the Operation Level to the Initial Setting Level.
*1 Set the PF Setting parameter to a-m (Auto/Manual).
*2 The No. 1 display will flash when the keys are pressed for 1 s or longer.
*3 Set the PF Setting parameter to pfdp (monitor/setting items).
Operation in progress
Stopped
Calibration Level
000
Control stops.
Advanced Function
Setting Level
Advanced settings
Communications
Setting Level
Power ON
Initial Setting Level
Operation Level
Adjustment Level
Monitor/Setting
Item Level
Press O and M Keys
for at least 1 s.
Starting in manual mode
Level changes
automatically.
Press O Key
for less than 1 s.
Protect Level
Manual Control
Level
Used to set the MV
manually.
Used for SPs and other
basic settings and
monitoring.
Press O Key for at
least 3 s while a-m is
displayed.
*2
Used to set protection
for operations.
Enter the password
(1201) for the Move to
Calibration Level
parameter.
Used to set the input type
and other basic settings.
Press S Key.
*3
Used to display
specified monitor and
setting items.
Press O or
S Key for at least 1 s.
*1
Program Setting
Level
Parameter and
segment settings for
all programs
Press S Key
for at least 1 s.
*1
Press O
Key for at
least 1 s.
Press O Key
for less than 1 s.
Press O Key
for less than 1 s.
Press O Key
for less than 1 s.
PID Setting
Level
Parameters for all PID
sets (e.g., PID
constants)
Adjustment parameters
(e.g., PID constants for
current PID set)
Press O Key for
at least 3 s.
*2
Press S Key.
*3
Press O Key for less
than 1 s (only models
with communications).
Press O Key for at
least 1 s.
Communications settings
Release protection and then
enter the password (−169) for
the amoV (Move to Advanced
Function Setting Level)
parameter.
Press O and M Keys
for at least 3 s.
*2