5 Advanced Operations
5 - 38
E5@C-T Digital Temperature Controllers User’s Manual (H185)
*1 If you change the same parameters in the Adjustment Level, they will apply to the parameters in the
currently selected PID set.
*2 You cannot set this parameter in PID set 8. For a temperature input with a sensor setting range, it will
always be set to the upper limit of the input indication range. For an analog input, it will always be set to
105.0%.
*3 Set the value to between 0% and 100% of the input setting range. If the PID Set Automatic Selection Data
parameter is set to DV, the unit is %FS.
• Parameters for Specifying Automatic Selection of PID Sets
*1 Set the value to between 0% and 100% of the input setting range. If the PID Set Automatic Selection Data
parameter is set to DV, the unit is %FS.
PID * Integral
Time (Cooling)
*1
*.c-i Same as PID * Integral Time.
PID
Setting
Level
PID * Derivative
Time (Cooling)
*1
*.c-d Same as PID * Derivative Time.
PID * Dead
Band
*1
*.cdb
Temperature input: -199.9 to 999.9 °C or °F 0.0
Analog input: -19.99 to 99.99 %FS 0.00
PID * Manual
Reset Value
*1
*.ofr 0.0 to 100.0 % 50.0
PID * MV Upper
Limit
*1
*.olh
Standard, close position-proportional: MV
lower limit + 0.1 to 105.0
% 100.0
Heating/cooling: 0.0 to 105.0 % 100.0
PID * MV Lower
Limit
*1
*.oll
Standard, close position-proportional: -5.0 to
MV upper limit − 0.1
%
0.0
Heating/cooling: -105.0 to 0.0 -100.0
PID * Automatic
Selection Range
Upper Limit
*2
*.aut
Temperature input: -1999 to 9999 EU 1320
Analog input: -5.0 to 105.0
%
*3
105.0
PID * LBA
Detection Time
*.lba 0 to 9999 (0: LBA function disabled) Seconds 0
Parameter name Display Setting range Unit Default Level
PID Set No. pid
0: Automatic selection
1 to 8: PID set number for manual setting
--- 1
Program
Setting Level
PID * Automatic
Selection Range
Upper Limit
(*: set number 1
to 7)
*.aut
(*: 1 to
7)
Temperature input: -1999 to 9999 EU 1320
PID Setting
Level
Analog input: -5.0 to 105.0 %
105.0
*1
PID Set
Automatic
Selection Data
pidi
pv: Automatic selection with PV
dv: Automatic selection with deviation
(PV - SP)
sp: Automatic selection with SP
--- pv
Advanced
Function
Setting Level
PID Set
Automatic
Selection
Hysteresis
pidh 0.10 to 99.99 %FS 0.50
Advanced
Function
Setting Level
Parameter
name
Display Setting range Unit Default Level