5-22 Logic Operations
5
5-22-2 Using Logic Operations
Operating Procedure
This procedure outputs alarm 1 status to auxiliary output 1 during
operation (RUN). A library object is used to make the setting.
1. Select Logic Operation
Editor from the CX-Thermo
tree, and click the Start
Button.
2. Click the Import of Library
Button.
3. Select Library 1 from the
library list, and then click the
OK Button.
Check the following settings:
Work Bit 1 Operation Type =
Operation 1, Work Bit 1
Input Assignment A = 9
(alarm 1), Work Bit 1 Input
Assignment B = 19 (invert
for Run/Reset), Work Bit 1
Input Assignment C = 0
(always OFF), Work Bit 1
Input Assignment D = 0
(always OFF), Auxiliary
Output 1 = Work bit 1.
Alarm 1
Run/Reset
Work bit 1
Always OFF Always OFF