6 Parameters
6 - 20
E5@C-T Digital Temperature Controllers User’s Manual (H185)
This parameter is set to one of the input values (X) in the alarm type list (page 3-19).
pid
PID Set No. Control must be set to 2-PID control.
• This parameter sets the PID set number for the specified program number.
• If this parameter is set to 0, the automatic PID set selection function will automatically
select the PID set number to be used in control according to the PV, DV, and SP.
z Related Sections
5-13 Using PID Sets (page 5-37)
al-1
Alarm Value 1
Alarms 1 to 4 must be assigned.
The alarm 1 to 4 type must not be set to 0, 1, 4, 5, or
12.
al-2
Alarm Value 2
al-3
Alarm Value 3
al-4
Alarm Value 4
• These parameters set the alarm value for alarms 1 to 4 of the specified program number.
• For a temperature input, the decimal point is automatically set according to the selected
sensor. For an analog input, the decimal point is set according to Decimal Point
parameter setting.
Alarms Other Than an MV Alarm
MV Alarms
z Related Parameters
Input Type (Initial Setting Level): Page 6-56
Scaling Upper Limit, Scaling Lower Limit, Decimal Point (Initial Setting Level): Page 6-57
Alarm 1 to 4 Type (Initial Setting Level): Page 6-66
Standby Sequence Reset (Advanced Function Setting Level): Page 6-83
Auxiliary Output 1 to 4 Open in Alarm (Advanced Function Setting Level): Page 6-84
Alarm 1 to 4 Latch (Advanced Function Setting Level): Page 6-89
Function
Setting
Setting range Unit Default
0 to 8 --- 1
See
See
Function
Setting
Setting range Unit Default
−1999 to 9999 EU 0
Setting range Unit Default
−199.9 to 999.9 % 0.0
See
See