2 Preparations
2 - 4
E5@C-T Digital Temperature Controllers User’s Manual (H185)
z E5AC-T
• Waterproofing is not possible when group mounting several Controllers.
• The recommended panel thickness is 1 to 5 mm for the E5CC-T, and 1 to 8 mm for E5EC-T, and
E5AC-T.
• Controllers must not be closely mounted vertically. (Observe the recommended mounting space
limits.)
• When two or more Digital Controllers are mounted, make sure that the surrounding temperature does
not exceed the allowable operating temperature specified in the specifications.
* For E5EC-T models with two control outputs (QQ, QR, CQ, RR, CC, or PR) and 019, 020, 021, or 022
options (shown below), the ambient temperature for group mounting must be 45°C max.
To mount these models at an ambient temperature of 55°C, install them at the following intervals.
Individual Mounting
120 min.
+1.0
0
Group Mounting
(96 × number of Units − 3.5)
92
+0.8
0
92
+0.8
0
92
+0.8
0
E5EC-T-@@ @ @ @ M-@@@
QQ, QR,
RR, CC, CQ, PR
019, 020,
021, 022
45
+0.6
0
92
120 min.
+0.8
0
60 min.