94
Initial Setting Level Section 5-5
5-5 Initial Setting Level
This level is for setting up the basic specifications of the E5AZ/E5EZ. In this
level, you can set the “input type” parameter for selecting the sensor input to
be connected to the E5AZ/E5EZ, limit the setting range of set points or set the
alarm mode.
To move from the operation level to the initial setting level, press key for
three seconds or more.
The initial setting level is not displayed when “initial setting/communica-
tions protect” is set to “2”. This initial setting level can be used when “initial
setting/communications protect” is set to “0” or “1”.
The “scaling upper limit”, “scaling lower limit” and “decimal point” parame-
ters are displayed when analog input is selected as the input type.
Power ON
Operation
Level
Initial Setting
Level
Control in progres
s
Control stopped
Control stopped
Press
3 seconds
or longer
Press Key
first display flicker
Press
1 second
or longer
25
100
C