E5CK
5–47
Transfer output type
Transfer output upper limit
Transfer output lower limit
Conditions of Use
The transfer output function must be in
use.
Ă• These parameters set the transfer output conditions.
Ă• The transfer output type" parameter selects one of the following data items as the
transfer output type, and assigns this to transfer output:
Present SP, Process value, Manipulated variable (heat), Manipulated variable (cool)
(during heating and cooling control)
Ă• The transfer output upper limit" and transfer output lower limit" parameters are
used for scaling of transfer output. The setting range varies according to this output
data. Also, a lower limit value larger than the upper limit value may be set.
Ă• During temperature input, the decimal point position of the set point or process value
is dependent on the currently selected sensor, and during analog input on the results
of scaling.
Ă• Set the scaling of the present SP or process value within the sensor input indication
range.
Transfer Output Type
Transfer Output Lower Limit to
Transfer Output Upper Limit
“ ”
Present SP
-1999 to 9999
“ ”
Process Value
-1999 to 9999
“ ”
Manipulated variable (heat)
-5.0% to 105.0% (standard control), 0.0 to 105.0% (heating
and cooling control)
“ ”
Manipulated variable (cool)
0.0 to 105.0%
Ă• Default : [ ].
ĂRelated description
4.9 How to Use Transfer Output (page 4Ć21)
ĂOption units
E53ĆCKF
Option Mode
Function
Setting
See
Model