E5CK
5–47
Transfer output type
Transfer output upper limit
Transfer output lower limit
Conditions of Use
The transfer output function must be in
use.
Ă These parameters set the transfer output conditions.
Ă The transfer output type" parameter selects one of the following data items as the
transfer output type, and assigns this to transfer output:
Present SP, Process value, Manipulated variable (heat), Manipulated variable (cool)
(during heating and cooling control)
Ă The transfer output upper limit" and transfer output lower limit" parameters are
used for scaling of transfer output. The setting range varies according to this output
data. Also, a lower limit value larger than the upper limit value may be set.
Ă During temperature input, the decimal point position of the set point or process value
is dependent on the currently selected sensor, and during analog input on the results
of scaling.
Ă Set the scaling of the present SP or process value within the sensor input indication
range.
Transfer Output Type
Transfer Output Lower Limit to
Transfer Output Upper Limit
Present SP
-1999 to 9999
Process Value
-1999 to 9999
Manipulated variable (heat)
-5.0% to 105.0% (standard control), 0.0 to 105.0% (heating
and cooling control)
Manipulated variable (cool)
0.0 to 105.0%
Ă Default : [ ].
ĂRelated description
4.9 How to Use Transfer Output (page 4Ć21)
ĂOption units
E53ĆCKF
Option Mode
Function
Setting
See
Model

Table of Contents

Other manuals for Omron E5CK

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron E5CK and is the answer not in the manual?

Omron E5CK Specifications

General IconGeneral
BrandOmron
ModelE5CK
CategoryController
LanguageEnglish

Related product manuals