5-11 Loop Burnout Alarm (Not Supported for Position-proportional Models.)
5
5-11-1 Loop Burnout Alarm (LBA)
Detection is not possible if a fault occurs that causes a decrease in temperature while control is
being applied to decrease the temperature (e.g., a heater burnout fault).
Parameters Related to Loop Burnout Alarms
A loop burnout alarm can be output by setting the alarm 1 type to 12 (LBA).
A setting of 12 (LBA) can be set for alarms 2 to 4, but the setting will be disabled.
Loop burnouts are not detected during SP ramp operation.
Loop burnouts are not detected during auto-tuning, manual operation, or while stopped.
If the alarm 1 latch is set to ON, the latch will be effective for the loop burnout alarm.
Loop burnouts are not detected during remote SP operation.
Automatically Setting the LBA Detection Time
The LBA detection time is automatically set by auto-tuning.
(It is not set automatically, however, for heating/cooling control.)
If the optimum LBA detection time is not obtained by auto-tuning, set the LBA Detection Time
parameter (Advanced Function Setting Level).
Determining the LBA Detection Time
To manually set the LBA detection time, set the LBA Detection Time parameter to twice the LBA
reference time given below.
(1) Set the output to the maximum value.
(2) Measure the time required for the width of change in the input to reach the LBA band.
(3) Set the LBA Detection Time parameter to two times the measured time.
LBA Level
Set the control deviation when the control loop is working properly.
Parameter
name
Display Setting range Remarks Level
LBA Detection
Time
lba 0 to 9999 (s)
Setting 0
disables the LBA
function.
Advanced
Function Setting
Level
LBA Level lbal
Temperature input 0.1 to 999.9 (°C/°F) Default: 8.0
(°C/°F)
Analog input 0.01 to 99.99
(%FS)
Default: 10.00%
FS
LBA Band lbab
Temperature input 0.0 to 999.9 (°C/°F) Default: 3.0
(°C/°F)
Analog input 0.00 to 99.99
(%FS)
Default: 0.20%
FS
PV
MV = 100%
Temperature
Time
Measurement time
Tm
LBA band
LBA detection time = Tm × 2

Table of Contents

Other manuals for Omron E5GC

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron E5GC and is the answer not in the manual?

Omron E5GC Specifications

General IconGeneral
BrandOmron
ModelE5GC
CategoryTemperature Controller
LanguageEnglish

Related product manuals