6 Parameters
6 - 64
E5@C Digital Temperature Controllers User’s Manual (H174)
rest
Standby Sequence Reset Alarm 1 to 4 type must be 5, 6, 7, 10, or 11.
This parameter selects the conditions for enabling reset after the standby sequence of the
alarm has been canceled.
Output is turned OFF when switching to the Initial Setting Level, Communications Setting
Level, Advanced Function Setting Level, or Calibration Level.
Condition A
Control started (including when the power supply is turned ON), and an alarm value
(alarm value upper/lower limit), the process value input shift, the process value slope
coefficient, or the SP changed. However, the standby sequence will not be restarted if the
SP is changed with a remote SP.
Condition B
Power ON
The following example shows the reset action when the alarm type is lower-limit alarm
with standby sequence.
Related Parameters
Alarm 1 to 4 Type (Initial Setting Level): Page 6-48
Alarm 1 to 4 Latch (Advanced Function Setting Level): Page 6-71
Function
Alarm
(after change)
Alarm
SP change
Condition A only
Alarm hysteresis
: Standby sequence canceled
: Standby sequence reset
Alarm output:
Condition A
Alarm output:
Condition B
Condition A
only
Setting
Setting range Default
a: Condition A, b: Condition B a
See
See