Error Descriptions
Event name Control Power Supply Undervoltage Event code 04A8 0000 hex
Description
The voltage between the positive and negative terminals in the control power supply converter dropped
below the specified value.
Source
EtherCAT Master Function Module
Source
details
Slave Detection
timing
Continuously
Error
attributes
Level
Minor fault
Recovery
Error reset
(after resetting slave
errors)
Log category
System
Effects
User program
Continues. Operation Power drive circuit is OFF for relevant slave.
Indicators
EtherNet/IP NET RUN EtherNet/IP NET ERR EtherNet/IP LINK/ACT
–––
System
-defined
variables
Variable Data type Name
None – –
Cause and
correction
Assumed cause Correction Prevention
Power supply undervoltage. Or,
the power supply voltage dropped
because there was inrush current
when the main power supply was
turned ON.
Increase the power supply
capacity.
None
A momentary power interruption
occurred.
Review the power supply
conditions and prevent momentary
power interruption.
Make sure that the power supply
conditions prevent momentary
power interruption.
The Servo Drive failed. Replace the Servo Drive. None
Attached
information
None
Precautions/
Remarks
“11” is displayed on the Servo Drive front panel and F011 is given as the AlarmCode (4001 hex).