1027
Network Instructions Section 3-25
d) Inner Board (CS Series only):
E1 hexadecimal
e) Computer: 01
Note It is also possible to directly specify a serial port (unit address) within the des-
tination device.
Serial Port Unit Addresses:
• Serial Communications Unit ports
Port 1: 80 hex + 4
× unit number
Port 2: 81 hex + 4
× unit number
• Serial Communications Board ports
Port 1: E4 hex (228 decimal)
Port 2: E5 hex (229 decimal)
•CPU Unit ports
Peripheral port: FD hex (253 decimal)
RS-232C port: FC hex (252 decimal)
Network Communications
Patterns
The following examples show three types of network communications: com-
munications from a PLC to other devices in a network, communications from a
Unit number
(hexadecimal)
Destination device
00
Unit number +10
E1
01
Node number
Node number
Node number
Node number
Inner Board
CPU Unit
Serial Communications Unit
Serial port 1
Serial port 2
Serial port 1
Serial port 2
Serial port 2 (Peripheral)
Serial port 1 (RS-232C)
Unit number0123456789ABCDEF
Hexadecimal 8084888C9094989CA0A4A8ACB0B4B8BC
Decimal 128 132 136 140 144 148 152 156 160 164 168 172 176 180 184 188
Unit number0123456789ABCDEF
Hexadecimal 8185898D9195999DA1A5A9ADB1B5B9BD
Decimal 129 133 137 141 145 149 153 157 161 165 169 173 177 181 185 189