1273
Model Conversion Instructions (Unit Ver. 3.0 or Later) Section 3-35
3-35-4 MOVE BIT: MOVBC(568)
Purpose Transfers the specified bit.
Ladder Symbol
Variations
Applicable Program Areas
Operands C: Control Word
The rightmost two digits of C indicate which bit of S is the source bit and the
leftmost two digits of C indicate which bit of D is the destination bit.
Operand Specifications
D00100
D00101
D00109
Stack area
Stack
pointer
Stack
data area
Bs
COLLC
Of
D
D00100
D00300
#8010
Stack area
Stack area
Allocated stack
After 1
st
execution
After 2
nd
execution
Of
8
010
0 0 0 1
1 2 3 4
0 0 0 0
LIFO
Read
5 6 7 8
1 2 3 4
0 0 0 2
D00102
D00300
5 6 7 8
1 2 3 4
S
C
D
MOVBC(568)
S: Source word or data
C: Control word
D: Destination word
Variations Executed Each Cycle for ON Condition MOVBC(568)
Executed Once for Upward Differentiation @MOVBC(568)
Executed Once for Downward Differentiation Not supported
Immediate Refreshing Specification Not supported
Block program areas Step program areas Subroutines Interrupt tasks
OK OK OK OK
15 8 07
C
Source bit: 00 to 15
(Two-digit BCD)
Destination bit: 00 to 15
(Two-digit BCD)
mn
Area S C D
CIO Area CIO 0000 to CIO 6143
Work Area W000 to W511
Holding Bit Area H000 to H511
Auxiliary Bit Area A000 to A959 A448 to A959
Timer Area T0000 to T4095
Counter Area C0000 to C4095
DM Area D00000 to D32767
EM Area without bank E00000 to E32767