205
Sequence Output Instructions Section 3-4
Description When the execution condition is ON, OUTB(534) turns ON bit N of word D.
When the execution condition is OFF, OUTB(534) turns OFF bit N of word D.
If the immediate refreshing version is not used, the status of the execution
condition (power flow) is written to the specified bit in I/O memory. If the imme-
diate refreshing version is used, the status of the execution condition (power
flow) is written to the Basic Output Unit’s output terminal as well as the output
bit in I/O memory.
OUTB(534) is supported by CS1-H, CJ1-H, and CJ1M CPU Units only.
Flags There are no flags affected by this instruction.
Precautions Immediate refreshing (!OUTB(534)) can be specified. An immediate refresh
instruction updates the status of the output terminal just after the instruction is
executed on an output bit allocated to a Basic Output Unit (but not for C200H
Group 2 Multi-point Output Units or Basic Output Units on Slave Racks), at
Timer Area T0000 to T4095
Counter Area C0000 to C4095
DM Area D00000 to D32767
EM Area without bank E00000 to E32767
EM Area with bank En_00000 to En_32767
(n = 0 to C)
Indirect DM/EM addresses in
binary
@ D00000 to @ D32767
@ E00000 to @ E32767
@ En_00000 to @ En_32767
(n = 0 to C)
Indirect DM/EM addresses in
BCD
*D00000 to *D32767
*E00000 to *E32767
*En_00000 to *En_32767
(n = 0 to C)
Constants --- #0000 to #000F (binary)
or &0 to &15
Data Registers DR0 to DR15
Index Registers ---
Indirect addressing using
Index Registers
,IR0 to ,IR15
–2048 to +2047, IR0 to –2048 to +2047, IR15
DR0 to DR15, IR0 to IR15
,IR0+(++) to ,IR15+(++)
,–(– –) IR0 to, –(– –) IR15
Area D N
15 0
D
N
ON
OFF
ON
OFF
This bit is turned OFF.
Execution condition
Bit N of word D

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron SYSMAC CJ - REFERENCE MANUAL 08-2008 and is the answer not in the manual?

Omron SYSMAC CJ - REFERENCE MANUAL 08-2008 Specifications

General IconGeneral
BrandOmron
ModelSYSMAC CJ - REFERENCE MANUAL 08-2008
CategoryController
LanguageEnglish

Related product manuals